< Back to listRB-TAP seriesPerfluorohexanone self-induction fire extinguishing belt

RB-TAP series

Perfluorohexanone self-induction fire extinguishing belt

Product specifications:

Specifications can be customized, usually 1000×50×1mm, 1000×100×1mm

Product introduction:

Perfluorohexanone self-induction fire-extinguishing belt is an innovative product to suppress cable fire.The belt is composed of nano-ceramic and perfluorohexanone microcapsule polymerization, perfluorohexanone microcapsules burst in case of fire to release perfluorohexanone gas, cooling fire extinguishing, the effect is far better than the traditional power cable flame retardant tape,fire retardantcoating.

  • Product Features
  • Technical Parameters
  • Application scenarios
  • Installation Notes
1.Cooling and cooling, rapid heat dissipation,rapid fire extinguishing, fire-resistant temperature, fire-resistant time, carbonization height(less than 0.2 m) and other key indicators have great advantages;
2.When the re-burning occurs, the fire can be repeatedly suppressed;
3.The fire-fighting gas released is clean and environment-friendly, and has no influence on the surrounding equipment
4.Simple construction, small material consumption, cost-effective;
5.The colors are customizable. The usual colors are yellow, green, red, blue, black, white, brown, etc. 

                

Performance indicators

Typical values

1

Trigger temperature

120±5℃

2

Appearance quality

The color is even and flat, without obvious flow mark,crack,bubble,

hole,scratch and defect,etc.

3

Jet Time

≤3s

4

High temperature performance(85±2°C/24h)

During the high temperature test,there is no false action,no softening and 

deformation after the test

5

LOW temperature performance(-40±2°C/24h)

During the low temperature test,there is no false action and

 no brittle fracture after the test

6

Air aging resistance

No crack or other damage after test

7

Salt spray corrosion resistance

No obvious corrosion damage after the test

8

Class B fire extinguishing performance

Extinguish fire within 8s after spraying

9

Class A fire extinguishing performance

After spraying, fire was extinguished within 9s; 

after extinguishing the openfire,the fire was restrained for 10min,

the space ventilation was opened, and the wood crib did not re-ignite

10

Volume resistivity of fire extinguishing belt

≥1.0×1011Ω•m

11

The volume resistivity of the fire-extinguishing 

belt ejecting gas

≥1.0×1010Ω•m

Apply to power,rail transit, new energy, mobile communications, petrochemical, metallurgical, large-scale buildings, such aswire, cable, joints of fire suppression, rapid fire.